150W Single Output Industrial DIN RAIL
EDR-150-24
SPECIFICATION
MODEL
EDR-150-24
DC VOLTAGE
24V
RATED CURRENT
6.5A / 230VAC 5.2A / 115VAC
CURRENT RANGE
0 ~ 6.5A / 230VAC 0 ~ 5.2A / 115VAC
RATED POWER
156W / 230VAC 125W / 115VAC
RIPPLE & NOISE (max.) Note.2 150mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
24 ~ 28V
VOLTAGE TOLERANCE Note.3 ±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±1.0%
SETUP, RISE TIME
1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
16ms/230VAC 10ms/115VAC at full load
VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE
47 ~ 63Hz
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
87%
2.6A/115VAC
20A/115VAC
1.7A/230VAC
35A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
PROTECTION
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed / 230VAC
105 ~ 150% rated output power
Protection type : Hiccup mode or constant current limiting, recovers automatically after fault condition is removed / 115VAC
OVER VOLTAGE
29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
Shut down o/p voltage, re-power on to recover
-20 ~ +60(Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85, 10 ~ 95% RH
SAFETY &
EMC
(Note 4)
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
±0.03%/(0 ~ 50)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH
Compliance to EN55022 (CISPR22) Class A, EN61000-3-2, Class A (80% Load), EN61000-3-3
OTHERS
NOTE
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
472.5K hrs min. MIL-HDBK-217F (25)
DIMENSION
40*125.2*113.5mm (W*H*D)
PACKING
0.6Kg; 20pcs/13Kg/1.16CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:EDR-150-24-SPEC 2014-07-07