M-Series Circuit Breaker - General Specifications | 3
Electrical Tables
Table A: Lists UL Recognized and CSA Accepted configurations & performance capabilities as a Component Supplementary
Protector.
Circuit
Configuration Max
Rating
32
50 2
65
65 1,2
65
Series
80 1
125
250 2
250
250
M-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
Voltage
Current Rating
Short Circuit Capacity (Amps)
Frequency
Phase
Full Load
Amps
Poles
General Breaking
Purpose Amps
UL / CSA
With Backup Without Backup
Fuse
Fuse
DC
---
0.02 - 15
---
---
15.1 - 25
1
1
---
---
DC
--- 0.02 - 7.5
---
1
---
0.02 - 15
---
2
---
DC
---
---
15.1 - 25
2
---
1000
1000
1000
1000
1000
0.02 - 15
---
1
---
DC
---
---
15.1 - 30
1
---
1000
1000
0.02 - 15
---
2
5000 3
---
DC
---
---
15.1 - 25
2
5000 3
---
0.02 - 15
---
1
---
600
DC
---
---
15.1 - 30
1
---
600
0.02 - 15
---
1
---
1000
50 / 60 1
---
15.1 - 30
1
---
1000
1 - 30
---
1
---
360
50 / 60 1 0.02 - 12
---
1
---
1000
50 / 60 1
---
12.1 - 18
1
1000 4
---
0.02 - 15
---
2
---
1000
50 / 60 1
---
15.1 - 30
2
---
1000
1 - 30
---
2
---
360
Application Codes
UL
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL0, U1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL1, C1
TC1, 2, OL0, C1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, OL1, U2
TC1, 2, OL1, U1
TC1, 2, OL0, C1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, OL1, U2
CSA
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL0, U1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL1, C1
TC1, 2, OL0, C1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC3, OL1, U3
TC1, 2, OL1, U1
TC1, 2, OL0, C1
TC1, 2, OL1, U1
TC1, 2, OL0, U1
TC3, OL1, U3
Notes:
1 Polarity Sensitive
2 Available only with Special Catalog Number. Consult Factory.
3 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 30 Amps maximum
4 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 60 Amps maximum
Table B: Lists UL Recognized,CSA Accepted and TUV and VDE Certified configurations and performance capabilities as a
Component Supplementary Protector.
Circuit
Configuration Max
Rating
32
50 2
65
65 3
Series
80 1
125
250
M-SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTORS
Voltage
Current Rating
Frequency
Phase
Full Load
Amps
General
Purpose
Amps
Short Circuit Capacity (Amps)
Poles
UL / CSA
Breaking With Without
Backup Backup
Fuse Fuse
VDE / TUV
With Without
Backup Backup
Fuse Fuse
Application Codes
UL
CSA
DC
---
0.02 - 15 ---
--- 15.1 - 25
1
1
---
1000 3000 500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
---
1000 3000 500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
DC
--- 0.02 - 7.5 ---
1
---
1000 3000 500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
0.02 - 15 ---
2
---
1000 3000 500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
DC
---
--- 15.1 - 25 2
---
1000 3000 500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
0.02 - 15 ---
2
5000
---
3000 500 TC1, 2, OL1, C1 TC1, 2, OL1, C1
DC
---
---
15.1 - 30 2
5000
---
3000 500 TC1, 2, OL0, C1 TC1, 2, OL0, C1
0.02 - 15 ---
1
---
600 4
---
500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
DC
---
--- 15.1 - 30 1
---
600 4
---
500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
0.02 - 15 ---
50 / 60 1
1 - 15
---
1
---
1000 3000 500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
1
---
360
3000 500 TC1, OL1, U2 TC3, OL1, U3
0.02 - 12 ---
1
---
1000 3000 500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
50 / 60 1 0.02 - 20 ---
2
---
1000 3000 500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
1 - 12
---
1
---
360
3000 500 TC1, OL1, U2 TC3, OL1, U3
Notes:
1 Polarity Sensitive
2 Available only with Special Catalog Number. Consult Factory.
3 Requires Branch Circuit Backup with a UL Listed type K-5 or RK-5 fuse rated 30 Amps maximum
4 TUV only, not VDE
5 Requires backup protection with a thermal magnetic circuit breaker rated 32 amps and having a
Type C trip characteristic per EN60898/DIN VDE 0641 (C32A) for ratings greater than 15amps,
and a thermal magnetic circuit breaker rated 16 amps and having a Type C trip characteristic per
EN60898/DIN VDE 0641 (C16A) for ratings 15 amps and less
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com

Share Link: 

datasheetq.com  [ Privacy Policy ]Request Datasheet ] [ Contact Us ]