DatasheetQ Logo
Electronic component search and free download site. Transistors,MosFET ,Diode,Integrated circuits

KAC-10 Ver la hoja de datos (PDF) - Unspecified

Número de pieza
componentes Descripción
Fabricante
KAC-10
ETC
Unspecified ETC
KAC-10 Datasheet PDF : 20 Pages
1 2 3 4 5 6 7 8 9 10 Next Last
High Speed Fuses
North American — FWA 150V: 70-1000A
FWA
Specifications
Description: North American style
stud-mount fuses.
Dimensions: See Dimensions
illustrations.
Ratings:
Volts: — 150Vac
Amps: — 70-1000A
IR: — 100kA Sym. (70-400A)
— 200kA Sym. (450-1000A)
— 20kA @150Vdc (70-800A)
— 100kA @ 80Vdc (70-400A)
Agency Information: CE, UL Recognized
Electrical Characteristics
Total Clearing I2t
1.5
The total clearing I2t at rated
K
voltage and at power factor of 1.0
15% are given in the electri-
cal characteristics. For other
0.5
voltages, the clearing I2t is
1)
found by multiplying by cor-
rection factor, K, given as a 0.3
0.2
2)
function of applied working
voltage, Eg, (rms).
0.15
22
70 102
Eg
150
1) 500-1000A Range
2) 70-400A Range
Dimensions (in)
Fig. 1: 70-400A
2.656
2.188
1.936
1.156
0.750 0.312
Fig. 2: 500-1000A
3.500
2.438
1.250
1.000
0.406
1mm = 0.0394 “ / 1” = 25.4mm
1.000
0.438
0.125
1.500
0.250
Arc Voltage
This curve gives the peak
UL
arc voltage, UL, which may 300
appear across the fuse dur-
ing its operation as a func-
tion of the applied working 200
voltage, Eg, (rms) at a
power factor of 15%.
100
Power Losses
Eg
Watts loss at rated current
50
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The correc-
1.0 Kp
0.8
0.6
0.5
0.4
0.3
tion factor, Kp, is given as 0.2
a function of the RMS load
current, Ib, in % of the
rated current.
0.1
30 40 50 60
Catalog Numbers
Electrical Characteristics
Rated
I2t (A2 Sec)
Catalog
Current
Clearing
Number
RMS-Amps Pre-arc
at 150V
FWA-70B
70
470
4000
FWA-80B
80
670
6000
FWA-100B
100
1200
12000
FWA-125B
125
1870
18000
FWA-150B
150
2700
26000
FWA-200B
200
4780
45000
FWA-250B
250
7470
70000
FWA-300B
300
10760
100000
FWA-350B
350
15700
140000
FWA-400B
400
20300
180000
FWA-500A
500
39000
120000
FWA-600A
600
46000
140000
FWA-700A
700
75000
220000
FWA-800A
800
92000
280000
FWA-1000A
1000
170000
510000
• Watts loss provided at rated current.
• See accessories on page 106.
100
150
Ib
70 80 90 100%
Watts
Loss
6.9
7.7
9.0
11.2
13.5
17.6
22.5
27.0
30.6
35.2
35.0
47.0
49.0
58.0
60.0
Features and Benefits
• Excellent dc performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
93