Standard Terminal Construction
1
1
2
3
4
Vinyl
Insulated
6
5
7
8
9
10
2
4
6
7
8
10
3
Nylon Insulated
with Insulation
Grip
5
9
3M Terminals provide a variety of design features assuring
consistently effective, reliable performance and easy
installation.
Please refer to the illustrations at the numbered locations
for the attributes described below.
1. One-piece, burr-free construction provides maximum
electrical conductivity. Electrical bright-tin plating gives
maximum corrosion resistance. Annealing relieves stress
points and assures maximum installed strength.
2. Barrel-to-pad transition design minimizes flexing
and bending.
3. Open-end design permits visual inspection of wire
location before and after crimping.
4. Maximum hold on wire comes from multiple “V”
grooves in #26-4 AWG parts, resulting in excellent
current flow.
5. Injection-molded insulations on terminals are the highest
quality in the industry.
• 221°F (105°C) rated, tough, resistant electrical
grade materials
• Molding ensures consistent wall thickness for
maximum reliability after crimping
• Molding allows funnel barrel construction for
easier installation
• Molding offers the crimp ridge and non-slip ridge
6. Crimp ridge designed for positive location of tool on
terminal barrel, resulting in few miscrimps.
7. Funnel barrel construction provides:
• Positive, easy wire insertion
• No hang-ups of wire strands
• Wire twisting not necessary
8. Nylon-insulated terminals, with grip, feature a brass
sleeve. Sleeve provides optimum grip on insulation,
strain relief and vibration protection. Brass sleeve is
recessed, which provides excellent flash-over protection.
9. Non-slip ridge so tool slides to correct position for a
proper crimp and better workmanship.
10.Beveled leading edge for easy wire insulation entry.
Barrel Styles
Non-insulated butted seam
The most economical terminal, it is
used where special performance or
installation characteristics are not
needed. Beveled mouth facilitates wire insertion.
Maximum temperature for bare terminals: 347°F (175°C).
Non-insulated brazed seam
Beveled mouth facilitates wire
insertion. Can be crimped anywhere
on barrel surface. Silver brazed seam
will not open under crimping pressure
or operating stresses. Unlike butted seam parts, stranded
wire cannot escape barrel confines during, or after, crimping.
Maximum temperature for bare terminals: 347°F (175°C).
Vinyl insulated brazed and butted seams
Used where insulated barrel
is necessary and desirable.
Terminal consists of brazed
or butted part with flared,
rigid molded polyvinyl
chloride sleeve, securely attached and funneled for easy wire
entry. Wire insulation positions itself against funnel portion
of vinyl sleeve, eliminating strand hang-up. Crimping barrel
and flared portion of sleeve provide excellent electrical
contact plus mechanical stress relief at junction of insulation
and barrel. Insulation has a non-slip ridge for ease of
positioning crimping tool.
Industry standard color coding indicates wire range.
Insulators are rated at a continuous operating temperature
range from -40°F to 221°F (-40°C to 105°C).
UL Listed and CSA Certified for 600V building wire
and 1,000V signs and lighting fixtures (luminaries).
Nylon insulated butted seam
with insulation grip
Used where insulated barrel
and positive insulation grip
are necessary or desirable.
Terminal consists of butted
seam part with flared, seamless brass sleeve securely
attached and covered with flared, molded nylon sleeve. Wire
insulation positions itself against funnel portion of brass
sleeve. Crimping barrel and flared portion of sleeve provide
excellent electrical contact plus mechanical stress relief at
junction of insulation and barrel. Positioning crimp tool is
nearly mistake proof due to a “step” in nylon insulation.
Industry standard color coding indicates wire range.
Insulators are rated at a continuous operating temperature
range from -40°F to 221°F (-40°C to 105°C).
UL Listed and CSA Certified for 600V building wire
and 1,000V signs and lighting fixtures (luminaries).