It should be noted that protection
tripping and blocking signals are not
routed via the K-Bus. Separate
conventional cabling is used for this
purpose; where appropriate the
isolated 48V dc supply available on
each relay is used to energise the
optically-isolated inputs.
Relay 32 Relay 4
Relay 3
Relay 2
Relay 1
Communications protocol
The communications protocol used
with K Range relays is designated
Courier. The Courier language has
been developed specifically for the
purpose of developing generic PC
programs that will, without
modification, communicate with any
device using the Courier language.
In the Courier system, all information
resides within the relay. Each time
communication is established with the
relay, the requested information is
loaded to the PC. The protocol
includes extensive error checking
routines to ensure the system remains
reliable and secure.
Figure 4: Basic communication system
Protocol
converter
RS232
KITZ
K-Bus
Desktop
computer
PC
Password protection
Password protection is provided on
settings which alter the configuration
of the relay, any accidental change to
which could seriously affect the ability
of the relay to perform its intended
function, ie. enable/disable settings,
protection function characteristic
selection, scheme logic settings and
system VT and CT ratios.
K bus screened
2 core cable
Figure 5: Typical communications terminal arrangement